P.max 0.5-6 bar
DN 15-20-25-32-40-50
Normally closed, manual reset solenoid valves for gas, suitable to shut off gas both to signal danger sent by gas detectors (methane, LPG, carbon monoxide and similar) or safety thermostats, and in the event of a power cut.
For additional safety, this solenoid valve can only be reset with the power supply on and only when the gas detector is not signalling danger.
IMPORTANT NOTE: The valve will not open by simply powering the coil. You must manually press the reset mechanism.
They can be equipped with CPI switches to control the valve’s obturator position (closed) remotely. Further information regarding the CPI switch is available in 7.0.
Reference standards: EN 161 - EN 13611.
In compliance with: