VICO - VICP - VIC
P.MAX 1 BAR
Safety valve with positive action, not operated by external power, manufactured with the aim to intercept the fuel flow to the burner to avoid the water temperature, on the delivery circuit of the system, reach the boiling temperature value.
The closure of the valves is caused by:
Capillary and/or bulb sensor puncture or cut. WARNING: Being positive action valves in this case it is not possible to reset the valve anymore.
Increasing of the water temperature till reaching the setted. In this case it is possible to reset the valve only if the temperature decreases of at least 10°C from the setting value stated on the product label
According to the Directive PED 2014/68/EU
(ex 97/23/EC)
I.N.A.I.L. Certified and calibrated
Certified according to "RACCOLTA R" ediction of 2009 - Application technical specifications of DM 1.12.75 Titolo II.
Together with every single valve an original copy of the calibration verbal is supplied.
This document, in addition of the valve technical documentation, contains also the registration number reported in the seal too fixed on the body valve. The document is sealed and validated by the I.N.A.I.L. technician who attended the calybration. We suggest to keep it very carefully as in case of loss it is not possible to release any copies.